Engine Model | LY20V170-T1 | ||
Enginepower | kW | 1298 | |
Rated speed | r/min | 1500 | |
Average effective pressure | MPa | 1.17 | |
Exhaust gas temperature | ºC | ≤550 | |
Wet exhaust gas flow rate | About | kg/h | 7442 |
Combustion air flow rate | ±8% | kg/h | 7120 |
Intake temperature after | ±5 | ºC | 50 |
Ventilation capacity | About | kg/h | 36957 |
Engine technical parameters | |||
/Cylinder Diameter/Stroke | mm | 170/195 | |
Displacement | dm3 | 88.5 | |
Average piston speed | m/s | 9.75 | |
Lubricant capacity | dm3 | 300 | |
Average consumption rate of lubricant at full load | g/kWh | ≤0.3 | |
Alternator | |||
Efficiency | % | 96.3 | |
Energy Balance | LY2000GL-T1 | ||
5)Output electric power5) | kW | 1250 | |
High-temperature coolant heat | ±8% | kW | 1099 |
Low temperature coolant heat | ±8% | kW | 115 |
120ºC Exhaust gas cooling to 120°C heat | ±8% | kW | 708 |
Engine radiant heat | About | kW | 48 |
Heat radiated by the alternator | About | kW | 48 |
Gas consumption | ±5% | kW | 3492 |
Electricity efficiency | % | 35.8 | |
Thermal efficiency | % | 51.8 | |
Total efficiency | % | 87.6 | |
System Parameters | |||
/High temperature coolant min/max flow | m3/h | 70/90 | |
Kvs EngineKvsValue | m3/h | 46 | |
Low temperature coolant flow | m3/h | 45 | |
Kvs IntercoolerKvsValue | m3/h | 72 | |
Engine Coolant Capacity | dm3 | 210 | |
Intercooler coolant capacity | dm3 | 52 | |
/High temperature coolant temperature inlet/outlet | ºC | 76/88.5 |